“x% of the generated energy for DHW was met by the heating element.”
→ Select a heat pump with higher power.
“x% of the generated energy for space heating was met by the heating element.”
→ Select a heat pump with higher power.
“The power of the heat pump plus heating element (x kW) is not sufficient to meet the heating load (y kW).”
→ Select a heat pump with higher power.
“Drilling depth must be less than or equal to the maximum drilling depth.”
→ Click the sizing button.
“The total length of the probe, X m, is too long or too short by Y%.”
→ Modify the parameters – within possible ranges – and then click on the sizing button until no more warning messages are shown.
“The ground has cooled by x% after one year. Please check the design.”\ → Reduce extraction power and/or increase heating element power.
“Please select a system with a heating buffer tank.”
→ Please note: if you select another system, all dependent values will be reset.
“The range of the radiator heating is too large to be supplied by the heat pump.”
→ Select a different heat pump or, if possible, revert to low-temperature heating.
“x% of the energy required for domestic hot water ’ + #13#10 + ’ could not be supplied!”
→ Increase the power of the heat pump (select a different heat pump) or reduce DHW requirement (less meaningful solution, as cold showers are not the intention).
“x% of the space heating requirement could not be supplied!”
→ Increase the power of the heat pump (select a different heat pump) or reduce the space heating requirement (less meaningful solution, as freezing is not the intention).
“For x weeks a year, y kWh of the space heating requirement could not be supplied!”
→ If the annual energy balance shows no shortfall, there may be shortfalls on a weekly basis.
Depending on the level of the shortfall, the power of the heat pump must be increased (select another heat pump) or the space heating requirement reduced.
“For x weeks a year, y kWh of the domestic hot water requirement could not be supplied!”
→ If the annual energy balance shows no shortfall, there may be shortfalls on a weekly basis.
Depending on the level of the shortfall, the power of the heat pump must be increased (select another heat pump) or the DHW requirement reduced.